Leave Your Message

I-69kV 4200kVA 5250kVA Isiguquli samandla seSigaba esi-3

Uvavanyo lweVoltage oluPhambili: 110kv, 115kv, 121kv okanye ezinye
Uvavanyo lweVolthi yesiBini: 11/10.5/6.6/6.3kV okanye ezinye
Uluhlu lwe-HV TAP: ±8×1.25% okanye ezinye
UHLOBO LOQHAGAMSHELWANO: YNd11 okanye abanye
UHLOBO: i-transformer efakwe kwi-oyile okanye i-substation transformer

    Ingcaciso yeMveliso

    I-69kV 4200kVA 5250kVA Isiguquli samandla seSigaba esi-3
    Iitransformer zamandla ze-110 kV ze-115 kV ngokwemigangatho
    1. Ingcaciso ye-GB 6451 kunye neemfuno zobugcisa zee-transformers zamandla ezintywilisiweyo kwi-oyile;
    2. Ii-IEC 60076 Power Transformers;
    3. Ii-Power Transformers ze-AS NZS 60076;
    4.CSAC88-16 Iitransformer zamandla;
    5. ANSI/IEEE C57.12.00 Umgangatho we-IEEE weeMfuno eziQhelekileyo zoSasazo oluNyibilikisiweyo, Amandla, kunye neeTransformers eziLawulayo;
    6. Ii-Power Transformers ze-GOST R 52719 - Iinkcukacha eziQhelekileyo;
    7. EN60076 Isiguquli samandla;
    8. Iinkonzo zasekhaya emva kokuthengisa eMntla Melika, uMzantsi Melika kunye neminye imimandla ziyaphendula kwiimfuno zakho kwiiyure ezingama-24.
    Isiguquli se-115kV
    I-SF11-20000/115 yi-115 kV 20 MVA power transformer, enikezelwa yi-JZP Transformer. Le transformer ithobela imigangatho yemveliso engqongqo ye-ANSI C57 Std. Inomthamo we-voltage ephezulu ye-115 kV kunye nomlinganiselo we-voltage ephantsi ye-13.8 kV.
    I-JZP Transformer izisa amava amaninzi kunye nerekhodi eliqinisekisiweyo kwiiprojekthi ze-transformer ezine-voltage ephezulu kwimarike yaseMelika. Amaqela abo obuchwephesha kunye namaqela okuthengisa abonisa ukuqonda okunzulu kwemithetho yasekuhlaleni kunye nokuthobela imigangatho ye-ANSI, IEEE, kunye ne-CSA. Ii-transformer ze-HV zeDaelim Transformer zifumene usetyenziso oluphumelelayo kwiindawo ezahlukeneyo zokufakelwa kulo lonke elase-United States, eKhanada, eMexico, eOstreliya, e-Ecuador, nakwamanye amazwe.
    Isiguquli se-115kV
    Iimpawu zeTransformer ye-115 kV 20 MVA
    I-Voltage: Le transformer isebenza kwi-115 kV kwaye inomthamo omkhulu we-20 MVA.
    I-Oil Conservator: Ixhotyiswe nge-oil conservator ukuze isebenze kakuhle kwaye ihlale ixesha elide.
    Uphawu lweVektha yeQela: I-transformer ilandela uphawu lwevektha yeDyn1 yeqela.
    Iindlela Zokupholisa: Isebenzisa inkqubo yokupholisa eguquguqukayo, kuquka iindlela ze-ONAN, ONAF1, kunye ne-ONAF2. Ukulinganiswa kwamandla kwahlukile phantsi kwezi ndlela: i-12 MVA ye-ONAN, i-16 MVA ye-ONAF1, kunye ne-20 MVA enamandla ye-ONAF2.
    Amanqanaba okukhusela: Inqanaba lokukhusela elinombane ophezulu libekwe kwi-550 kV, ngelixa inqanaba lokukhusela elinombane ophantsi liyi-110 kV.
    Uvavanyo lobushushu: Le transformer yenzelwe ukusingatha ukunyuka kobushushu obuphezulu obujikelezayo obuyi-65℃ kunye nokunyuka kobushushu beoyile obuphezulu obuyi-55℃.
    I-Tap Changer: Icala le-HV liqhayisa nge-tap changer eneendawo ezi-5 ezahlukeneyo, evumela amanqanaba amahlanu olawulo lwe-voltage ngaphakathi koluhlu lwe-±2×2.5%.
    Ii-Bushings: Ii-bushings eziphezulu neziphantsi ze-voltage zifakelwa lula phezulu.
    Izithinteli zokuVula: Ukuze kubekho ukhuseleko oluphuculweyo nokhuseleko, icala le-voltage ephezulu lixhotyiswe ngezithinteli zokuVula ezintathu.
    Iimpawu zeTransformer ye-115 kV 20 MVA
    Isiguquli se-110kV 115kV
    Iitransformer zamandla ze-115kV/110kV ziyilwe kwaye ziphuculwe ngokufunxa nokusebenzisa ubuchwepheshe obuphambili ngaphakathi nakwamanye amazwe ukuze kuphuculwe i-transformer core, i-coil, umzimba, iilead, itanki yepetroli, kunye nezinye izinto, ezibonisa ukukhutshwa okuncinci kwenxalenye, ilahleko ephantsi, ingxolo ephantsi, ilula, kunye nokuthembeka okuphezulu. Ukusebenza kwayo okuhle kakhulu kuye kwafumana udumo olukhulu kubasebenzisi kunye neengcali ezifanelekileyo. Le mveliso ineempawu zozinzo, uqoqosho, kunye nokukhuselwa kwendalo, kwaye ifanelekile kwizityalo zamandla, izitishi ezincinci, amashishini amakhulu emizi-mveliso kunye noosomashishini abasakha izimbiwa, njl.njl.
    Isiguquli se-110kV 115kV
    Uvavanyo kunye neZifundo
    I-transformer ye-115 kV 20 MVA idlula kuthotho olupheleleyo lovavanyo ukuqinisekisa ukuba iyahlangabezana nemigangatho engqongqo ebekwe yi-ANSI C57. Ezi vavanyo ziquka:
    Ukulinganiswa kokufakwa kwe-insulation
    Ukulinganiswa koMlinganiselo weVoltage kunye neVector Group
    Ukulinganiswa kweeParameters zokuVula
    Uvavanyo lokumelana neVoltage yoMthombo oNgahlukileyo
    Ukulinganiswa koMbane weBushing kunye neDielectric Dissipation Factor
    Uvavanyo lokumelana neVoltage yeMpembelelo yokukhanyisa
    Uvavanyo lokuxhathisa i-Induction Over Voltage kunye noVavanyo lokuKhutshwa okuNgaphelelanga
    Ukulinganiswa kweVoltage ye-Impedance kunye nokulahleka komthwalo
    Uvavanyo lweZero-Sequence Impedance Ukulinganisa iNqanaba leNgxolo
    Uvavanyo lweSitywino soxinzelelo Uvavanyo lokunyuka kobushushu
    Ukulinganiswa kweKreyivu yeMpendulo yeSpektri yeFrekhi yokuVutha
    Uvavanyo lwangoku lwePolarity Test Dimension Test
    Olu vavanyo luqinisekisa ukuba i-transformer ye-115 kV iyahambelana nemigangatho ye-ANSI C57 kwaye ifanelekile ngokupheleleyo, iqinisekisa ukuthembeka nokusebenza kwayo.
    Uvavanyo kunye neZifundo
    Iinkcukacha zeTransformer yamandla ye-110kV kunye ne-115kV
    I-110kv I-duplex power winding transformer enama-phase amathathu kwi-load changer
    Uvavanyo I-Voltage edibeneyo Akukho Kulahleka Komthwalo Ukulahlekelwa ngumthwalo Akukho Mthwalo wangoku Impendance yesekethe emfutshane
    (kVA) HW I-LV
    6300 kVA 110kV ±8 6.3kv 10 36 0.8 10.5
    8000 kVA ×1.25% 6.6 kW 12 45 0.8
    10000 kVA   10.5kv 14.2 53 0.74
    12500 kVA 115kV ±8 11kv 16.8 63 0.74
    16000 kVA ×1.25%   20.2 77 0.69
    20000 kVA     24 93 0.69
    25000 kVA     28.4 110 0.64
    31500 kVA     33.8 133 0.64
    40000 kVA     40.4 156 0.58
    50000 kVA     47.8 194 0.58
    63000 kVA     56.8 234 0.52
    I-110kv I-transformer yamandla ejikelezayo yesigaba sesithathu kwi-load changer
    Uvavanyo I-Voltage edibeneyo Akukho Kulahleka Komthwalo Ukulahlekelwa ngumthwalo Akukho Mthwalo wangoku
    (kVA) I-HV(kV) I-MV(kV) I-LV(kV)
    6300 kVA 110kv±8 35kv 6.3kv 12 47 0.95
    8000 kVA ×1.25% 37kv 6.6 kW 14.4 56 0.95
    10 MVA   38.5kv 10.5kv 17.1 66 0.89
    12.5 MVA 115kv±8   11kv 20.2 78 0.89
    16MVA ×1.25%     24.2 95 0.84
    20MVA       28.6 112 0.84
    25MVA       33.8 133 0.78
    31.5MVA       40.2 157 0.78
    40MVA       48.2 189 0.73
    50MVA       56.9 225 0.73
    63MVA       67.7 270 0.67

    Buza Ngoku!

    Ukuba unemibuzo malunga neemveliso zethu okanye uluhlu lwamaxabiso, nceda usishiyele i-imeyile yakho kwaye siya kuqhagamshelana nathi kwiiyure ezingama-24.

    Leave Your Message